  1. Ensure RSLogix is in offline mode.
  2. Right click on the 1756-ENET/B Ethernet Bridge (or comparable) node and select “Add Module”.
  3. Select the module type “Generic Ethernet Module” and then click “OK”.
  4. Type an identifier for the Ethernet/IP communications module in the “Name” field.  This will identify controller tags.
  5. Under Comm Format select “Data - SINT”
  6. Click the “IP Address” radio button under the “Address/Host Name” label.  Enter the module IP address.
  7. Under the “Connection Parameters” label enter the following settings:

      Assembly InstanceSize (bytes)
    Input0x65 (101d)14
    Output0x66 (102d)22
    Configuration0x80 (128d)0
  8. Click the “Connection” tab in the Module Properties dialog box.
  9. In the “Requested Packet Interval (RPI)” field enter the value 10 (ms).
  10. Click “OK”.  The RSLogix environment is now configured to communicate with the EIP interface module.

 